0 items
in cart
$0.00
Electronics Retailer & Wholesaler, Australia

3RU BATTERY PACK TO SUITELSR10 - 75 UPSONIC

  • Code:

    33779342
  • Model:

    ESBP3RU
  • Brand:

  • Unit:

    Each
  • Stock:

    BUY-IN
  • +
Be the first to review!

Freight Estimator Enter 4 digit postcode


Your Price
$1573.00
Interested in purchasing this product?
This product is a special buy-in. Special buy-in products are goods specially bought in on customer's request. After acceptance, special buy-in products cannot be cancelled or the goods returned, unless Radio Parts and its supplier agrees to the cancellation of the corresponding order and return of goods. Prices are subject to change and in the event that our purchase price has changed, we will notify you before finalising your order. Please call us on 1800 337 366 for availability, ETA or if you have further questions.
Do you accept these conditions?
I ACCEPT

3RU Battery Pack for extended UPS run time

  • Designed to suit ESLR series. ( ESLR10 to ESLR75 )
  • Batteries not included.

This battery pack is available with 12V/7AH or 12V/9AH batteries the battery pack is also configured in either 24V/36V/48V depending on which model the battery pack is to be fitted too.

 

SPECIFICATIONS:

Line Interactive Sine wave output 1RU UPS Tower UPS Rack / Tower Option for UPS Long Run Time UPS require accompanying Battery Pack Batt Pack
Model Energy Saver Series (ES xxx) ES 1RU10 ES 1RU15 EST 10 EST 15 EST 20 ESRT 10 ESRT 15 ESRT 20 ESRT 30 ESRT 50 ESLR 10 ESLR 15 ESLR 20 ESLR 30 ESLR 50 ESLR 75 ES BP 3 RU
Capacity VA/Watt 1.0/625 1.5/938 1.0/625 1.5/938 2.0/1250 1.0/625 1.5/938 2.0/1250 3.0/1875 5.0/3125 1.0/625 1.5/938 2.0/1250 3.0/1875 5.0/3125 7.5/4688
Input Nominal Voltage 230 VAC
Voltage Range 170 VAC ~ 300 VAC
Frequency 45Hz - 70 Hz auto sensing
Boost Transfer 208 VAC ± 2%
Boost Return 218 VAC ± 2%
Buck Transfer 252 VAC ± 2%
Buck Return 242 VAC ± 2%
Low Voltage Transfer to Batt 190 VAC ± 2%
Low Voltage Return 200 VAC ± 2%
High Voltage Transfer to Batt 286 VAC ± 2%
High Voltage Return 276 VAC ± 2%
Output Wave Form Pure Sine Wave
Efficiency >80%
Overload Protection Line Mode >110% then buzzer alarm and amber LED continuously blinking
Battery Mode 110% ~ 150% for 30 seconds: >150% for 200ms, then UPS Shuts Down
Short Circuit Protection Line Mode Circuit Breaker
Battery Mode Electronic Circuit
Cold Start DC Start Yes
Transfer Time Typical <4ms
Battery Voltages 24VDC 24VDC 24VDC 36VDC 36VDC 24VDC 36VDC 36VDC 36VDC 48VDC 24VDC 36VDC 48VDC Various
Battery Amp 6V 9Ah 6V 9Ah 7.2Ah 7.2Ah 9Ah 7.2Ah 7.2Ah 9Ah 7.2Ah 9AH Requires ES BP 3 RU Batt Box 7.2 OR 9 Ah as required 16 x 7.2Ah or 9Ah
LCD Display UPS status;
I/P & O/P Voltage, frequency;
Load Level;
Battery voltage & Level;
internal temperaure Normal Green, Warning AmberFault RED
Audible alarm Battery Mode Beeping every 4 seconds
Low Battery Beeping every 1 second
UPS Fault Continuous Beep
Overload Beeping 2 x every second
Communications Interface Various combinations of RS232; SNMP;USB; Dry Contact & AS 400 available as options
Dimensions
(W/H/D in mm)
440/44/515 440/44/515 145/210/380 145/210/445 145/210/445 440/88/465 440/132/465 440/132/620 440/88/465 440/132/465 440/132/465
Net Weight Kg 18 20 16.5 17.5 22.5 16 17.5 24.5 36.9 49.8 16 17.5 24.5 25 34.6
Environment Operating Environment 0 - 40 Deg C Relative Humidity 0 - 95% Non Condensing
Noise Level Less than 55dBA (@1.0 Meter)
Outlets / Connections 4IEC 4IEC 3IEC 6IEC 10IEC 10IEC + TB 6IEC 10IEC 5IEC+Terminal Block